Step #1
Table 3.5: Demand Weight of Fixtures, in Fixture Units
Fixture Type
Occupancy
Weight in
Fixture Units
Number of
Fixtures
Total
Bathtub
Private
2
Bathtub
Public
4
Bedpan Washer
Public
10
Bidet
Private
2
Bidet
Public
4
Combo Sink & Tray
Private
3
Dental Unit / Cuspidor
Public
1
Dental Lav
Private
1
Dental Lav
Public
2
Drinking Fountain
Private
1
Drinking Fountain
Public
2
Kitchen Sink
Private
2
Kitchen Sink
Public
4
Lavatory
Private
1
Lavatory
Public
2
Laundry Tray
Private
2
Laundry Tray
Public
4
Shower- Each Head
Private
2
Shower- Each Head
Public
4
Sink, Service
Private
2
Sink, Service
Public
4
Urinal, Pedestal
Public
10
Urinal (Wall Lip)
Public
5
Urinal Stall
Public
5
Urinal w/ Flush Tank
Public
3
Wash Sink (Each Set of Faucets)
Public
2
Water Closet, Flush Valves
Private
6
Water Closet, Flush Valves
Public
10
Water Closet, Flush Tank
Private
3
Water Closet, Flush Tank
Public
5
Total Fixture Flow Units
STH-Logo-FINAL.White Vertical
  • Products
  • Manufacturers
  • Engineering
  • Parts
  • Contact
  • About

Recent Posts

97 Monocacy Blvd
Suite D
Frederick, MD 21701
P: (301) 682-3390
T: (800) 233-7718
F: (301) 682-3391

97 Monocacy Blvd
Suite D
Frederick, MD 21701
P: (301) 682-3390
T: (800) 233-7718
F: (301) 682-3391